Check Transformer

Possible Cause #

What to Check - Field #

Action Needed - Field #

  1. Be sure terminals are tight. Repair burnt wires accordingly.

  2. If wires check out, use a Volt meter to check for power on both sides of the transformer. Primary side black and white wires should read 110-120VAC.

  3. Secondary side the black w/white striped wires should read 24-26VAC. From each black w/white striped wires to the brown wire should read 12-13VAC.

  4. If none of the voltages are read, replace the transformer.

Caution #

Resolution

Did Check Transformer resolve the issue?

Yes, resolution code 105.

No, go to next step.


Tags: kb power electrical transformer